Impact of Condensation Temperature on Refrigeration Efficiency

       When the evaporation temperature remains unchanged, the condensation temperature or condensation pressure increases, and the compression ratio Po of the tube condenser increases, resulting in a reduction in the cooling capacity of the compressor and an increase in power consumption. Therefore, the condensation temperature has a great impact on the working efficiency of the refrigeration device.
       An important component of refrigeration equipment is tube condenser. As we all know, heat must be taken away by it. The two parameters of temperature and pressure are important basis for weighing the heat transfer effect. The condensation temperature and condensation pressure mainly depend on the cooling water temperature, water quality, water quantity and temperature of the surrounding medium, etc., and are related to the temperature rise of the cooling water in the equipment and the structure of the equipment. In addition, when it generates oil, scale and air accumulation, the water condensation area is not enough, the compressor exhaust temperature is too high, and the uneven distribution of cooling water will also increase the condensation temperature or condensation pressure.
       As the condensation temperature becomes higher, the exhaust temperature becomes higher, the cooling capacity of the refrigerator decreases, and the power consumption increases. When the condensation temperature is too high, it will not only make the operation of the refrigerator unsafe and easily cause accidents, but also reduce the working efficiency of the refrigeration device and the gas transmission coefficient of the compressor, and increase the shaft power, thus increasing production costs. Therefore, whether from the perspective of safety or consumption saving, we should strive to use low water temperature, sufficient water volume, good water quality and the selection of reasonable tube condensers to adjust the refrigeration system to work at a lower condensation pressure, and it is reasonable to use a lower condensation temperature.
1185 次

相关文档

Copy right © 2019 Wuxi Chemical Equipment Co., Ltd. All Rights Reserved Website Design: Wuxi Wangke