An air cooled heat exchanger does one thing very simply: it moves heat from a process fluid to the atmosphere. No cooling tower, no circulating water, no water treatment, no risk of a cooling water leak into the process. That simplicity is the reason these exchangers are common at remote sites, in arid regions, in small modular plants and in applications where water simply is not available.
The simplicity ends as soon as selection begins, because the air is a poor heat transfer fluid whose temperature, velocity and cleanliness are outside the designer's control. Choosing well means matching the bundle to the duty, the fans to the bundle and the whole arrangement to the site conditions.
Process fluid flows through tubes arranged in one or more horizontal rows. Each tube is fitted with fins that increase the surface exposed to the moving air. The warmed air leaves the bundle and is replaced by cooler ambient air, and the difference between those two air temperatures is the driving force for the whole heat transfer.
Because the driving force is small, usually a few degrees Kelvin, the required surface area is large. This is why an air cooled exchanger is physically big, and why the design is dominated by airflow rather than by the process side. The bundle area, the fin geometry and the air velocity are all chosen so that the required duty can be delivered within the available approach to ambient.
The two fundamental arrangements differ in how the air is moved.
Natural draft relies on the buoyancy of the hot air leaving the bundle. A tall chimney or a shaped canopy above the bundle creates the stack effect that draws air through the tubes. The moving parts are few, the power consumption is close to zero and the noise is minimal. The cost is that the airflow is not controllable in the way a fan makes it controllable, and the performance depends on the arrangement of the bundle and the shape of the stack. A well-designed natural draft unit can perform very well, but it is harder to derate and harder to predict than a fan-assisted one.
Forced fan units use axial or centrifugal fans to push or pull air across the bundle. Because the fan is a controllable device, the design can be verified against measured performance and adjusted seasonally. The price is electrical power, noise, mechanical wear and the need for a drive system that has to work reliably in an outdoor environment.
A mixed or induced draft arrangement, in which fans are used to boost buoyancy flow rather than to create it, is a compromise that is sometimes used on very large units.
The table below sets out the practical differences between the common arrangements. Figures are typical planning values and vary with the design, the site and the duty.
| Characteristic | Natural draft | Forced fan |
|---|---|---|
| Air movement | Buoyancy and induced chimney effect | Axial or centrifugal fan |
| Electrical consumption | Effectively none | Typically 0.5 to 4 kW per fan, depending on size |
| Noise | Low; dominated by airflow over the bundle | Higher; fan tone and blade passage are the main sources |
| Turndown capability | Limited; output follows ambient conditions | Good; fan speed or blade pitch can be trimmed |
| Susceptibility to wind | Meaningful; can be wind-assisted or wind-affected | Low if the fans are correctly positioned |
| Maintenance | Bundle cleaning and structure inspection | Bundle cleaning, fan bearings, belts or gearboxes, motor checks |
| Typical output per unit | From small duties up to very large ratings | From very small duties to large ratings |
| Best suited to | Remote sites, low noise limits, large duties, limited power availability | Small to medium duties, sites with reliable power, tight schedules |
Almost all air cooled exchangers use finned tubes, and the fin choice is decided by the environment rather than by the duty. Aluminium fins dominate because aluminium is cheap, light, easy to form and has good thermal conductivity. Aluminium-magnesium alloys are used where higher strength or better corrosion behaviour is needed. Steel or stainless steel fins appear where the atmosphere is aggressive, where cleaning is mechanical and severe, or where a non-sparking requirement applies.
Fin profiles include plain helical fins, serrated or lanced fins, and plate fins on some designs. Serrated fins increase the fin-to-air contact area and improve the heat transfer coefficient, but they trap dust more readily and are harder to clean. Plain fins clean more easily and are more forgiving in dusty service. The pressure drop also differs: serrated fins generally sit at the higher end of the pressure drop range.
The bundle itself is built from sections, and the number of tube rows and the number of bundles in series determine both the heat transfer performance and the pressure drop on the process side. A single row is compact and cheap but poor at recovering the full duty. Two rows are the common default. Three or four rows are used when the process pressure drop allowance is generous and a tight approach to ambient is needed, at the cost of a taller frame.
Heat exchangers with one pass and several tubes in parallel are the simplest arrangement. The circuit with a single pass and one tube in parallel gives the highest velocity and the highest heat transfer coefficient, but the highest pressure drop, and it needs the largest pump. Multiple passes in series and tubes in parallel give more length in a smaller frame and a lower pressure drop for a given duty, at the cost of maldistribution risk if the header design is poor.
Counter-current flow on the process side, in which the incoming and outgoing tubes are located in different positions in the bundle, is normally preferred for temperature-sensitive fluids because it produces a more uniform approach along the length of the bundle. Whether it is worth the additional piping complexity depends on the fluid and on how tight the design temperature must be held.
Fan power follows from the airflow and the pressure the bundle presents. Since the bundle pressure drop rises with the square of the velocity, a modest increase in air speed produces a disproportionate increase in fan power, and also increases noise and the fouling rate. This is the classic trade-off in air cooler design, and it is why the air velocity is usually kept moderate rather than maximised.
Axial fans are used on larger, low-pressure applications because they are efficient at moving large volumes of air against low resistance. Centrifugal fans are used where the pressure is higher, where the flow must be clean and free of recirculation, or where the fan is remote from the bundle. Multi-fan arrangements with variable speed drives allow seasonal control and can substantially reduce energy use, since the duty and the ambient temperature are both seasonal.
Noise has three sources: fan tone, airflow over the bundle and the structure itself. Fan tone is controlled by blade selection, tip speed and the number of fans. Structure-borne noise is controlled by isolators and by avoiding direct rigid connections. To keep the design within a site noise limit, the fan arrangement, the tip speed and the bundle inlet velocity have to be considered together, and it is far cheaper to set the limit at specification stage than to retrofit silencers later.
The output of any air cooled exchanger changes with ambient temperature, and this is unavoidable. A unit rated for a certain duty at a design ambient will deliver less at a higher ambient and more at a lower one. The approach temperature, the difference between the process outlet and the ambient air, is the parameter that captures this. A low approach needs a large bundle and a high air velocity, which raises fan power and noise. A high approach is cheap but means a warmer process outlet.
Two practical points follow. First, in winter the outlet temperature can fall far below what the process needs, so either the control system must bypass part of the exchanger or the design must include a control strategy that modulates the airflow. Second, in very hot climates the design ambient should be set to a realistic figure including a margin, since an under-sized margin is the most common cause of a shortfall in service.
The final selection is a site-specific judgement rather than a catalogue choice, and the following factors have to be evaluated together.
Air coolers are usually delivered as sections and erected on site, and the erection quality has a large effect on performance. Levelness of the frame and of the fan ring matters, because a fan running out of alignment delivers less air and vibrates. The clearance between the fan ring and the bundle must be set as designed, or the airflow becomes uneven. Louvers and wind screens, if fitted, must be checked for correct orientation and free movement. The whole structure should be checked for thermal expansion movement, because a rigidly braced frame can distort the bundle in a hot summer and permanently reduce performance.
Commissioning should verify airflow across the bundle and not just at the fan, confirm fan rotation direction and bearing condition, check the motor and the control system, and record the baseline coolant outlet temperature and process outlet temperature at the design conditions. The bundle should be inspected before the fans are started, since a damaged or misaligned fin will not be visible once the unit is running.
An air cooled heat exchanger trades water for air, and the whole design follows from that trade. Natural draft suits large duties, remote sites and strict noise limits with almost no power consumption; forced fan units suit smaller duties and offer the control and the derating options that a scheduled process requires. Within either arrangement the fin family, the number of tube rows and the fan arrangement decide the balance between approach temperature, power consumption, noise and cleanability. Specify the duty with a realistic design ambient, add a margin, and evaluate the noise and wind constraints at the same time as the thermal duty. A correctly selected and correctly erected unit will meet its nameplate rating in the conditions it was designed for.